1 - Define an OperationalLimit (PATL Current) for an Equipment ACTransmissionLine

OperationalLimitSet _b3e74f7e-f257-44f1-a558-39d2476dbc54
for Terminal _8372a156-7579-4ea5-8793-24caf0d24603
of ACTransmissionLine _1e7f52a9-21d0-4ebe-9a8a-b29281d5bfc9
Changed the Limit to directly refer to the Equipment
CurrentLimit PATL value is 525
Other terminal of the line has no limit defined


2 - Define an OperationalLimit (PATL Current) for an Equipment ACTransmissionLine that will be mapped to a DanglingLine in IIDM

OperationalLimitSet _57c14dc8-1249-4a1c-8a58-b741b7bd8ae5
Terminal _04684742-c766-11e0-2222-005056c00008 (corresponds to the end not in the boundary)
ACLineSegment with an end in the boundary _f32baf36-7ea3-4b6a-9452-71e7f18779f8 (XQ2-N5 in Sub4)
Change the Limit to directly refer to the equipment


3 - Define an OperationalLimit (PATL Current) for an Equipment PowerTransformer. It should be rejected

OperationalLimitSet _e5badf8e-cfbd-48f0-b248-adfa0eb9a884
Terminal _51ac3672-026d-4257-9c68-7c7f57a9b55e (T5_0, TransformerEnd 115 kV)
PowerTransformer _ceb5d06a-a7ff-4102-a620-7f3ea5fb4a51 (T5 in Substation Sub4)
CurrentLimit PATL value is 158
For the same power transformer, the other terminal has:
OperationalLimitSet _db22b997-1134-4ef1-a4ce-3d599b44de6a
Terminal _0fa430b4-d98c-43bd-9652-f61fb00e7340 (T5_1, TransformerEnd 10 kV) 
CurrentLimit PATL value is 1732
We have changed the limit of 115 kV end to Equipment instead of Terminal
It should be rejected 

 
4 - Define an OperationalLimit (PATL Current) for an Equipment of type Switch. It will not be assigned

OperationalLimitSet _4de221e3-af50-46de-b0d2-d096fc6bb7fc 
defined for Terminal T6_1 (10.5 kV)
Terminal _7145f995-b4a7-472e-9c58-2f8540ad3925 (T6_0, 115 kV)
Terminal _912cc25e-78d9-43a6-a77e-b2b7bb76688b (T6_1, 10.5 kV)
PowerTransformer _6c89588b-3df5-4120-88e5-26164afb43e9 (T6 on Sub4)
Assign to Switch _d0119330-220f-4ed3-ad3c-f893ad0534fb (BREAKER18 of T6)
Should be left unassigned